Design /

Below you can find more information about our Design

Hydraulic Calculations Hazen William Equation

Q=1002 x C x D2.65 x S0.54

Where:

Q flow rate M3/hr

C = 150 for HDPE

D is the internal Diameter of Pipe in Mtrs

S is friction loss in pipe line in mtrs/ mtr

Typical Hazen - Williams coefficients

Material C factor(low) C factor(high)
Asbestos Cement 135 140
Cast iron 100 140
Mortar lined D1 135 140
Concrete 100 140
Steel 90 110
Polythylene 145 150
PVC 145 150
GRP 140 150